RA-912F Portable SF6 Gas Comprehensive Analyzer
For determining the quality of SF6 gas.SF6 purity analyzer .SF6 Dew point analyzer and SF6 Decomposition product analyzer 3 in 1.
RA-912F allows the determination of up to three quality parameters with only one measurement:
SF6 concentration (%)
Moisture concentration
SO2 concentration (ppm)
1.Using the principle of SF6 gas spectral absorption measurements,
rapid, without the interference of other gas components to better meet the needs of the site.
2.SF6 purity mass ratio (g / g), volume ratio (mol/mol) switch at any time to display
can be directly controlled national standard, eliminating the volume and mass ratio conversion link.
3.Massive experimental data, based on real-time traffic temperature compensation.
4.Unique patented drying protection device.
5.Boot-up zero, the slope of the self-calibration.
6.Built-in gas filtration system
7.Each measuring gas path individually designed to ensure accuracy, independent regulation is more suitable for field use.
8.TFT touchscreen
9.Built-in printer
TECHNICAL DATA | |
---|---|
Dimensions | L 406 mm, W 538 mm, H 269 mm |
Weight | 15 kg |
Input pressure | 0.2 - 35 bar |
Operating temperature | -20 °C to +50 °C |
Ambient moisture | 15% up to 90 % relative moisture, non condensing during operation |
Operating voltage | 100-240 VAC, 50/60Hz |
Number of measured values to be stored | max.500 |
Interface | USB |
Drag left and right table
PURITY | MOISTURE | SO2 | H2S | CO | |
---|---|---|---|---|---|
Measuring principle | Thermal conductivity | Electronic moisture measurement (capacitive) | Electrochemical reaction | Electrochemical reaction | Electrochemical reaction |
Measuring range | 0 - 100 vol.% | -80 to +20 °C | 0 to 100 ppm 0 to 10 ppm0 to 2000ppm |
0 to 100 ppm | 0 to 500 ppm |
Measuring accuracy | ±2 %(F.S) | ±2 ℃ | ±5 % μL/L | ±5 % μL/L | ±5 % μL/L |
Flow rate | 250 to 350 mL/min Recommend 300 mL/min |
300 to 900 mL/min Recommend 500 mL/min |
100 to 120 mL/min Recommend 100 mL/min |
100 to 120 mL/min Recommend 100 mL/min |
100 to 120 mL/min Recommend 100 mL/min |
Reaction time | < 30 s | < 3 min | < 60 s | < 60 s | < 60 s |
Recommended calibration interval | every one years | every one years | every one years | every one years | every one years |